Dc= and dc³ (data register comparison), Dc= and dc ≥ (data register comparison) – IDEC MicroSmart User Manual

Page 200

Advertising
background image

7: B

ASIC

I

NSTRUCTIONS

7-16

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

DC= and DC

≥ (Data Register Comparison)

The DC= instruction is an equivalent comparison instruction for data register values. This instruction will constantly com-
pare data register values to the value that has been programmed in. When the data register value equals the given value, the
desired output will be initiated.

The DC

≥ instruction is an equal to or greater than comparison instruction for data register values. This instruction will

constantly compare data register values to the value that has been programmed in. When the data register value is equal to
or greater than the given value, the desired output will be initiated.

When a data register comparison instruction is programmed, two addresses are required. The circuit for a data register
comparison instruction must be programmed in the following order: the DC= or DC

≥ instruction, a data register number

D0 through D399 (all-in-one 10-I/O type CPU module) or D1299 (other CPU modules), or D2000 through D7999 (slim
type CPU modules); followed by a preset value to compare from 0 to 65535.

The preset value can be designated using a decimal constant or a data register D0 through D399 (all-in-one 10-I/O type
CPU module) or D1299 (other CPU modules), or D2000 through D7999 (slim type CPU modules). When a data register is
used, the data of the data register becomes the preset value.

• The DC= and DC≥ instructions can be used repeatedly for different preset values.
• The comparison instructions also serve as an implicit LOD instruction, and must be programmed at the beginning of a

ladder line.

• The comparison instructions can be used with internal relays, which are ANDed or ORed at a separate program

address.

• Like the LOD instruction, the comparison instructions can be followed by the AND and OR instructions.

Ladder Diagram (DC=)

Ladder Diagram (DC

≥)

Data register # to compare with

Preset value to compare

DC=
50

D2

DC>=
D15

D3

Instruction

Data

DC=

OUT

D2
50
Q0

Program List

Instruction

Data

DC>=

OUT

D3
D15
Q1

Program List

Q0

Q1

Ladder Diagram

Instruction

Data

DC=

OUT
LOD

AND

OUT

D5
10
M0
I0
M0
Q0

Program List

Ladder Diagram

Instruction

Data

DC=

AND
OUT

D5
10
I0
Q0

Program List

Instruction

Data

DC=

OR
OUT

D5
10
I0
Q0

Program List

Ladder Diagram

I0

I0

M0

DC=
10

D5

DC=
10

D5

I0

DC=
10

D5

M0

Q0

Q0

Q0

Advertising