IDEC MicroSmart User Manual

Page 333

Advertising
background image

20: P

ULSE

I

NSTRUCTIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

20-5

Timing Chart for Disable Pulse Counting

This program demonstrates a timing chart of the PULS2 instruction without pulse counting.

D1

M20

I1

PULS
2

S1

D100

D102 = 0 (disable pulse counting)

Output Pulse Q1

Output Pulse Frequency D101

FR1

FR1

Star t Input I1

• When input I1 is turned on, PULS2 star ts to generate output pulses at the frequency designated by the value

stored in data register D101. While the output pulses are sent out from output Q1, internal relay M20 remains on.

• When input I1 is turned off, PULS2 stops generating output pulses immediately, then internal relay M20 turns off

and internal relay M21 turns on.

• If the output pulse frequency value in D101 is changed while generating output pulses, the change takes effect in

the next scan. When changing the pulse frequency, make sure that the timing of the change is much slower than
the output pulse frequency, so that the pulse frequency is changed successfully.

FR2

FR3

Pulse Output ON M20

Pulse Output Complete M21

FR2