IDEC MicroSmart User Manual

Page 270

Advertising
background image

15: W

EEK

P

ROGRAMMER

I

NSTRUCTIONS

15-4

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

• Keep Output ON across 0 a.m.

When the hour/minute comparison data to turn on (S2) is larger than the hour/minute comparison data to turn off (S3), the
comparison ON output (D1) turns on at S2 on the day designated by S1, remains on across 0 a.m., and turns off at S3 on
the next day. This example demonstrates a program to keep the designated output on across 0 a.m. and turn off the output
on the next day.

• Keep Output ON for Several Days

Multiple WKTIM instructions can be used to keep an output on for more than 24 hours. This example demonstrates a pro-
gram to keep the designated output on from 8 a.m on every Monday to 7 p.m. on every Friday.

D1
Q0

S1
38

M8125

WKTIM
0

S2

2000

S3

600

M8125 is the in-operation output special internal relay.

S1 (38) specifies Monday, Tuesday, and Friday.

The WKTIM turns on output Q0 at 20:00 on Monday, Tuesday, and
Friday, and turns off output Q0 at 6:00 on the next day.

Sun

Mon

Tue

Wed

Thu

Fri

Sat

20:00

6:00

ON

Output Q0

20:00

6:00

ON

20:00

6:00

ON

D1

M0

S1

2

M8125

WKTIM
0

S2

800

S3

10000

M8125 is the in-operation output special internal relay.

S1 (2) specifies Monday.

S1 (28) specifies Tuesday, Wednesday, and Thursday.

S1 (32) specifies Friday.

S2 (10000) and S3 (10000) disable comparison of hour and
minute data.

While internal relay M0, M1, or M2 is on, output Q0 remains on.

Sun

Mon

Tue

Wed

Thu

Fri

Sat

20:00

19:00

ON

Output Q0

D1

M1

S1
28

WKTIM
0

S2

10000

S3

10000

D1

M2

S1
32

WKTIM
0

S2

10000

S3

1900

M0

M1

M2

Q0