Analog input parameters, Analog input parameters -11, I/o c – IDEC MicroSmart User Manual

Page 397

Advertising
background image

24: A

NALOG

I/O C

ONTROL

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

24-11

Analog Input Parameters

Analog input parameters include the analog input signal type, analog input data type, analog input minimum and maxi-
mum values, filter value, thermistor parameter, analog input data, and analog input operating status. This section describes
these parameters in detail.

Analog Input Signal Type

A total of 11 analog input signal types are available, depending on the analog I/O or analog input module. Select an analog
input signal type for each analog input channel. When a channel is not used, select the default value or

Not used

for the

channel.

Analog Input Data Type

A total of five analog input data types are available, depending on the analog I/O or analog input module. Select an analog
input data type for each analog input channel.

Binary Data

When Binary data is selected as an analog input data type, the analog input is linearly converted into digital data in the
range described in the table below.

Parameter

FC4A-

L03A1

FC4A-

L03AP1

FC4A-

J2A1

FC4A-

J4CN1

FC4A-

J8C1

FC4A-

J8AT1

0

Voltage input (0 to 10V DC)

X

X

X

X

1

Current input (4 to 20 mA DC)

X

X

X

X

2

Type K thermocouple

X

X

3

Type J thermocouple

X

X

4

Type T thermocouple

X

X

5

Pt 100 resistance thermometer

X

X

6

Pt 1000 resistance thermometer

X

7

Ni 100 resistance thermometer

X

8

Ni 1000 resistance thermometer

X

9

NTC type thermistor

X

10

PTC type thermistor

X

255

Not used

X

X

X

Parameter

FC4A-

L03A1

FC4A-

L03AP1

FC4A-

J2A1

FC4A-

J4CN1

FC4A-

J8C1

FC4A-

J8AT1

0

Binar y data

X

X

X

X

X

X

1

Optional range

X

X

X

X

X

X

2

Celsius

X

X

NTC only

3

Fahrenheit

X

X

NTC only

4

Resistance

X

Type No.

FC4A-L03A1
FC4A-L03AP1
FC4A-J2A1

FC4A-J4CN1

FC4A-J8C1

FC4A-J8AT1

Analog Input Data

0 to 4095

Analog Input Signal Type Analog Input Data

Voltage/Current:

0 to 50,000

Thermocouple:

0 to 50,000

Pt100, Ni100:

0 to 6,000

Pt1000, Ni1000:

0 to 60,000

0 to 50000

0 to 4000

Advertising