IDEC MicroSmart User Manual

Page 83

Advertising
background image

2: M

ODULE

S

PECIFICATIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

2-63

Communication Adapter and Communication Module Specifications

Note 1: RS485 user communication is available on upgraded CPU modules only, see page 17-1.

Note 2: Recommended cable for RS485: Twisted-pair shielded cable with a minimum core wire of 0.3 mm

2

.

Conductor resistance 85

Ω/km maximum, shield resistance 20 Ω/km maximum.

The proper tightening torque of the terminal screws on the RS485 communication adapter and RS485 communication mod-
ule is 0.22 to 0.25 N·m. For tightening the screws, use screwdriver SZS 0,4 x 2,5 (Phoenix Contact).

Installing the Communication Adapter and Communication Module

Communication Adapter

To install the communication adapter on the all-in-one type CPU module, open the hinged lid and remove the dummy car-
tridge. Push the communication adapter into the port 2 connector from the front until it bottoms and is secured by the
latches. Similarly, when installing the communication adapter on the HMI base module, open the hinged lid, and push the
communication adapter into the port 2 connector from the front until it bottoms and is secured by the latches.

Type No.

FC4A-PC1
FC4A-HPC1

FC4A-PC2
FC4A-HPC2

FC4A-PC3
FC4A-HPC3

Standards

EIA RS232C

EIA RS485

EIA RS485

Maximum Baud Rate

19,200 bps

19,200 bps

Computer link: 19,200 bps
User com.:

19,200 bps

Data link:

38,400 bps

Maintenance Communication
(Computer Link)

Possible

Possible

Possible

User Communication

Possible

Not possible

Possible (Note 1)

Modem Communication

Possible

Not possible

Not possible

Data Link Communication

Not possible

Not possible

Possible

Quantity of Slave Stations

31

Maximum Cable Length

Special cable

Special cable

200m (Note 2)

Isolation between Internal Circuit
and Communication Port

Not isolated

Not isolated

Not isolated

Caution

• Before installing the communication adapter or communication module, turn off the power to the

MicroSmart

CPU module. Otherwise, the communication adapter or CPU module may be dam-

aged, or the

MicroSmart

may not operate correctly.

Communication Adapter

Hinged Lid

Dummy Car tridge

After installing the communication adapter,
attach the dummy car tridge again.

Por t 2 Connector

Communication Adapter

Por t 2 Connector

Hinged Lid