I/o c – IDEC MicroSmart User Manual

Page 406

Advertising
background image

24: A

NALOG

I/O C

ONTROL

24-20

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Analog Output Module FC4A-K1A1 on Slot 3

Ladder Diagram

As shown in the ladder diagram below, when initialize pulse special internal relay M8120 is used for the ANST macro in
parallel with another instruction, load M8120 again for the other instruction.

Note: The above ladder diagram is only an example and should be modified as required.

DR Allocation Range

Designation

Description

D760 - D779

Automatic range allocation, 20 words

I/O

Channel

Item

Designation

Description

OUT

CH0

Signal Type

0 to 10V DC

Voltage output

Data Type

Binar y data

0 to 4095

M8120 is the initialize pulse special internal relay.

When the CPU star ts to run, ANST stores parameters to
data registers to configure analog I/O modules and Q30
is turned on.

When I0 is turned on, analog input data is moved from
D676 to D1000.

The temperature is compared with the alarm tempera-
ture of 100°C.

When the temperature is higher than 100°C, Q30 is
turned off.

When the temperature is not higher than 100°C, Q30 is
turned on.

Analog input data of –500 to +1500 is conver ted to 0 to
2000.

Analog input data of 0 to 2000 is conver ted to 0 to
4000.

Analog input data of 0 to 4000 is moved to D772 (ana-
log output data) of the analog output module.

M8120

REP

S1 –

D676

D1 –

D1000

MOV(I)

REP

S1 –

D1000

D1 –

D772

MOV(W)

REP

S1 –

D676

D1 –
M30

CMP>(I)

S2 –

1000

NO.1

J8AT1

NO.3

K1A1

ANST

Q30

S

Q30

R

Q30

S

M30

M30

I0

REP

S2 –

500

D1 –

D1000

S1 –

D1000

ADD(I)

REP

S2 –

2

D1 –

D1000

S1 –

D1000

MUL(W)

M8120

Advertising