As-i – IDEC MicroSmart User Manual

Page 476

Advertising
background image

28: AS-I

NTERFACE

M

ASTER

C

OMMUNICATION

28-36

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

HW Series Digital I/O Data Allocation

Input data is sent from slaves to the AS-Interface master. Output data is sent from the AS-Interface master to slaves.

Notes:

SwitchNet HW Series

Slave Unit

Used I/O

Communication

Block Mounting

Position

Input Data

(slave send data)

Output Data

(slave receive data)

DI3

DI2

DI1

DI0

DO3

DO2

DO1

DO0

Pushbutton

1 in

0

X1

1

1

*

Pilot light

1 out

0

0

1

1

*

X1

Illuminated pushbutton

1 in/1 out

0

X1

1

1

*

X1

Selector, Key selector: 2-position

1 in

0

X2

1

1

*

Selector, Key selector: 3-position

1 in

0

X3

1

1

*

1 in

0

X3

1

1

*

Illuminated selector: 2-position

1 in/1 out

0

X2

1

1

*

X1

Illuminated selector: 3-position

1 in

0

X3

1

1

*

1 in/1 out

0

X3

1

1

*

X1

1.

∗ The AS-Interface master uses bit DO3 for addressing A/B
slaves.

2.

In the above table, bits marked with X1, X2, and X3 are used
for SwitchNet I/O data.

3.

X1: When pushbutton is pressed, input data is 1 (on). When
not pressed, input data is 0 (off). When output data is 1 (on),
LED is on. When output data is 0 (off), LED is off.

4.

X2: The input data from 2-position selector, key selector, and
illuminated selector switches depend on the operator position
as shown below.

5.

X3: The input data from 3-position selector, key selector, and
illuminated selector switches depend on the operator position
as shown below.

As shown in the table and figure, 3-position selector, key
selector, and illuminated selector switches use two communi-
cation blocks. Each communication block must have a unique
address, therefore the 3-position selectors require 2 slave
addresses.

6.

Unused input bits DI3 and DI2 are 0 (off), and unused input
bits DI1 and DI0 are 1 (on). Slaves ignore unused output data
(—) sent from the master.

2-position Operator

Operator Position

Left

Right

DI2

0

1

3-position Operator

Operator Position

Left

Center

Right

Communication
Block Mounting

Position

Input Data Bit

DI2

1

0

0

DI2

0

0

1

Selector

Left

Right

Selector

Left

Right

Center

Address Marking Area

Mounting
Position

Mounting
Position

AS-Interface –

AS-Interface +

AS-Interface +

AS-Interface –

Communication Block Mounting Position

(Rear View)

On 3-position selector, key selector, and illuminated
selector switches, communication blocks

➀ and ➁

are mounted in positions shown above.

Write_Parameter Command

Write_Parameter Settings

0

0

A4

A3

A2

A1

A0

1

Sel

P3

P2

P1

P0

PB

1

LED

Brightness

Settings

Remarks

Output

Selection

Control Data

P2

P1

P0

100%

1: DO0
0: DO1

1

1

Default

50%

0

1

25%

1

0

12.5%

0

0

Advertising