User program protection – IDEC MicroSmart User Manual

Page 145

Advertising
background image

5: S

PECIAL

F

UNCTIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

5-25

User Program Protection

The user program in the

MicroSmart

CPU module can be protected from reading, writing, or both using the Function Area

Settings in

WindLDR

. The read/write protection can be temporarily disabled using a predetermined password.

Upgraded CPU modules with system program version 210 or higher have an option for read protection without a pass-
word, making it possible to inhibit reading completely.

Programming WindLDR

1. From the

WindLDR

menu bar, select Configure > Function Area Settings. The Function Area Settings dialog box

appears.

2. Select the Others tab.

3. Under Protect User Program, select required protect modes for Read Protect and Write Protect in the pull-down

list.

Unprotected:

The user program in the CPU module can be read and written without a password.

Password Protected:

Prevents unauthorized copying or inadver tent replacement of the user program.
The protection can be temporarily disabled using a predetermined password.

Prohibited:

Prevents copying of the user program completely.
This option is available for read protection only and can not be temporarily disabled using a
password. To select this option, use a CPU module with system program ver. 210 or higher
and WindLDR ver 5.31 or higher

• If the user program is read-protected without using a password, the read protection cannot be tem-

porarily disabled using the password, thus the user program cannot be read out by any means. To
disable the read protection, download another user program without user program protection.

Warning

• Before proceeding with the following steps, make sure to note the password, which is needed to

disable the user program protection. If the user program in the

MicroSmart

CPU module is write-

or read/write-protected, the user program cannot be changed without the password.