CNT, CDP, and CUD (Counter)

Three types of counters are available; adding (up) counter CNT, dual-pulse reversible counter CDP, and up/down selection
reversible counter CUD. A total of 32 counters (all-in-one 10-I/O type CPU module) or 100 counters (other CPU modules)
can be programmed in a user program. Each counter must be allocated to a unique number C0 through C31 or C99.

The valid operand range depends on the CPU module type. For details, see pages 6-1 and 6-2.
The preset value can be 0 through 65535 and designated using a decimal constant or data register.

CNT (Adding Counter)

When counter instructions are programmed, two addresses are required. The circuit for an adding (UP) counter must be
programmed in the following order: reset input, pulse input, the CNT instruction, and a counter number C0 through C99,
followed by a counter preset value from 0 to 65535.

The preset value can be designated using a decimal constant or a data register. When a data register is used, the data of the
data register becomes the preset value.

Counter

Allocation Number

Preset Value

CNT (adding counter)

C0 to C99

Constant:

0 to 65535

Data registers: D0 to D1299

D2000 to D7999

CDP (dual-pulse reversible counter)

C0 to C99

CUD (up/down selection reversible counter)

C0 to C99

Ladder Diagram

I2

Reset Input I0

ON

OFF

Pulse Input I1

ON

OFF

Counter C0

ON

OFF

Timing Chart

Output Q0

ON

OFF

1

Input I2

• • •

C0

2

3

4

5

6

ON

OFF

CNT

C0

5

I1

Reset

Pulse

Instruction

Data

LOD
LOD
CNT

LOD
AND
OUT

I0
I1
C0
5
I2
C0
Q0

Program List

I0

• The same counter number cannot be programmed

more than once.

• While the reset input is off, the counter counts the lead-

ing edges of pulse inputs and compares them with the
preset value.

• When the current value reaches the preset value, the

counter turns output on. The output stays on until the
reset input is turned on.

• When the reset input changes from off to on, the cur-

rent value is reset.

• When the reset input is on, all pulse inputs are ignored.
• The reset input must be turned off before counting may

begin.

• When power is off, the counter’s current value is held,

and can also be designated as “clear” type counters
using Function Area Settings (see page 5-4).

• Counter preset and current values can be changed

using

WindLDR

without downloading the entire pro-

gram to the CPU again. From the

WindLDR

menu bar,

select Online > Monitor, then select Online > Point
Write
. To change a counter preset value, specify the
counter number with a capital C and a new preset
value. To change a counter current value, specify the
counter number with a small c and a new current value
while the counter reset input is off.

• When the preset or current value is changed during

counter operation, the change becomes effective imme-
diately.

• For the data movement when changing, confirming,

and clearing preset values, see page 7-13. Preset values
can also be changed and changed preset values can be
confirmed using the HMI module. See pages 5-35 and
5-36.

• The preset value 0 through 65535 can be designated

using a data register D0 through D1299 or D2000
through D7999; then the data of the data register
becomes the preset value. Directly after the CNT
instruction, the OUT, OUTN, SET, RST, TML, TIM,
TMH, or TMS instruction can be programmed.

CNT

C28

D5

I1

Reset

Pulse

I0

Q0

Q0