IDEC MicroSmart User Manual

Page 73

Advertising
background image

2: M

ODULE

S

PECIFICATIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

2-53

FC4A-J2A1 (Analog Input Module) — Screw Terminal Type

Applicable Terminal Block:

FC4A-PMT11P (supplied with the analog input module)

FC4A-J4CN1 (Analog Input Module) — Screw Terminal Type

Applicable Terminal Block:

FC4A-PMT10P (supplied with the analog input module)

Terminal No.

Channel

+

24V DC

NC

NC

NC

IN0

+

NC

IN1

+

Connect a fuse appropriate for the applied voltage and current draw, at the position shown in the
diagram. This is required when equipment containing the MicroSmar t is destined for Europe.

Do not connect any wiring to unused terminals.

Fuse

+

24V DC

+

+

Analog voltage/current

output device

Analog voltage/current

output device

Terminal No.

Channel

24V

24V DC

0V

NC

CS

IN0

+

I–

CS

IN1

+

IN1

I–

CS

IN2

+

I–

CS

IN3

+

I–

Connect a fuse appropriate for the applied voltage and current draw, at the position shown in the diagram. This is
required when equipment containing the MicroSmar t is destined for Europe.

When connecting a resistance thermometer, connect three wires B, B’, and A to the CS (current sense), +, and – termi-
nals of input channels IN0 through IN3, respectively.

When connecting a thermocouple, connect the + wire to the + terminal and the – wire to the CS and – terminals.

Do not connect the thermocouple to a hazardous voltage (60V DC or 42.4V peak or higher).

Do not connect any wiring to unused terminals.

– terminals of input channels IN0 through IN3 are interconnected.

Fuse

+

24V DC

Analog voltage
output device

+

Resistance
thermometer

A

B

B’

Thermocouple

+

NC

+

NC

NC

Analog current
output device

Advertising