IDEC MicroSmart User Manual

Page 34

Advertising
background image

2: M

ODULE

S

PECIFICATIONS

2-14

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Function Specifications (Slim Type CPU Module)

CPU Module Specifications

Note 1: When using a 64KB memor y car tridge and WindLDR ver. 4.2 or higher.
Note 2: When using a CPU module with system program ver. 201 or higher and WindLDR ver. 4.2 or higher.

System Statuses at Stop, Reset, and Restart

Note: All expansion data registers are keep types. AS-Inter face operands (M1300-M1977 and D1700-D1999) remain
unchanged when the reset input is turned on.

CPU Module

FC4A-D20K3
FC4A-D20S3

FC4A-D20RK1
FC4A-D20RS1

FC4A-D40K3
FC4A-D40S3

Program Capacity

27,000 bytes
(4,500 steps)

31,200 bytes (5,200 steps)
64,500 bytes (10,750 steps) (Note 1, Note 2)

Expandable I/O Modules

7 modules

I/O Points

Input

12

Expansion: 128

12

Expansion: 224

24

Expansion: 224

Output

8

8

16

User Program Storage

EEPROM

RAM Backup

Backup Duration

Approx. 30 days (typical) at 25°C after backup batter y fully charged

Backup Data

Internal relay, shift register, counter, data register, expansion data register

Battery

Lithium secondar y batter y

Charging Time

Approx. 24 hours for charging from 0% to 90% of full charge at 25°C

Battery Life

Approx. 1000 cycles of discharging down to 10% and full charging

Replaceability

Not possible to replace batter y

Control System

Stored program system

Instruction Words

35 basic
53 advanced

35 basic
72 advanced

Processing
Time

Basic instruction

1.65 ms (1000 steps) See page A-1.

END processing

0.64 ms (not including expansion I/O ser vice, clock function processing, data
link processing, and interrupt processing) See page A-2.

Internal Relay

1024

1024 + 560 for AS-Inter face operands (Note 2)

Shift Register

128

Data Register

1300

1300 + 300 for AS-Inter face operands (Note 2)

Expansion Data Register

6,000

Counter

100 (adding, dual pulse reversible, up/down selection reversible)

Timer

100 (1-sec, 100-ms, 10-ms, 1-ms)

Input Filter

3 to 15 ms (selectable in increments of 1 ms)

Catch Input
Interrupt Input

Four inputs (I2 through I5) can be designated as catch inputs or interrupt inputs
Minimum turn on pulse width: 40 µs maximum
Minimum turn off pulse width: 150 µs maximum

Self-diagnostic Function

Power failure, watchdog timer, data link connection, user program EEPROM sum
check, timer/counter preset value sum check, user program RAM sum check,
keep data, user program syntax, user program writing, CPU module, clock IC, I/O
bus initialize, user program execution

Start/Stop Method

Turning power on and off
Star t/stop command in WindLDR
Turning star t control special internal relay M8000 on and off
Turning designated stop or reset input off and on

Mode

Output

Internal Relay, Shift Register, Counter,

Data Register, Expansion Data Register

Timer Current Value

Keep Type

Clear Type

Run

Operating

Operating

Operating

Operating

Stop (Stop input ON)

OFF

Unchanged

Unchanged

Unchanged

Reset (Reset input ON)

OFF

OFF/Reset to zero

OFF/Reset to zero

Reset to zero

Restar t

Unchanged

Unchanged

OFF/Reset to zero

Reset to preset

Advertising