Operation basics, Operation basics -6, As-i – IDEC MicroSmart User Manual

Page 446

Advertising
background image

28: AS-I

NTERFACE

M

ASTER

C

OMMUNICATION

28-6

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Operation Basics

This section describes simple operating procedures for the basic AS-Interface system from programming

WindLDR

on a

computer to monitoring the slave operation.

AS-Interface System Setup

The sample AS-Interface system consists of the following devices:

AS-Interface Cable Wiring

Before wiring the AS-Interface cable, remove the AS-Interface cable terminal block from the AS-Interface cable connector
on the AS-Interface master module.

AS-Interface specifies use of brown cables for the AS-Interface + line, and blue cables for the AS-Interface – line. Connect
the cables to match the color labels on the terminal block. Tighten the terminal screws to a torque of 0.5 to 0.6 N·m.

Insert the terminal block to the connector on the AS-Interface master module, and tighten the mounting screws to a torque
of 0.3 to 0.5 N·m.

Name

Type No.

Description

FC4A MicroSmart Slim Type CPU Module

FC4A-D20RK1

MicroSmart AS-Interface Master Module

FC4A-AS62M

WindLDR

FC9Y-LP2CDW

Version 5.0 or higher

AS-Interface Standard Slave

1 unit
Address 0
ID: 0, I/O: 7, ID2: F, ID1: 7

AS-Interface Power Supply

PS2R-Q30ABL

Output 30.5V DC, 2.4A (73W)

Slim Type CPU Module

FC4A-D20RK1

AS-Inter face Master Module
FC4A-AS62M

Standard
AS-Inter face Cable

Computer Link Cable 4C
FC2A-KC4C
3m (9.84 ft.) long

AS-Interface Power Supply

Standard Slave
Address 0
ID: 0, I/O: 7, ID2: F, ID1: 7

Blue AS-Inter face –

Use a ferrule.

Brown AS-Inter face +

Use a ferrule.

Blue Label

Brown Label

Advertising