background image

2: M

ODULE

S

PECIFICATIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

2-25

AC Input Module Specifications

Type No.

FC4A-N08A11

Input Points and Common Lines

8 points in 2 common lines

Terminal Arrangement

See Input Module Terminal Arrangement on page 2-29.

Rated Input Voltage

100 to 120V AC (50/60 Hz)

Input Voltage Range

85 to 132V AC

Rated Input Current

17 mA/point (120V AC, 60 Hz)

Input Type

AC input, Type 2 (IEC 61131-2)

Input Impedance

0.8 k

Ω (60 Hz)

Turn ON Time

25 ms

Turn OFF Time

30 ms

Isolation

Between input terminals in the same common: Not isolated
Between input terminals in different commons: Isolated
Between input terminals and internal circuits: Photocoupler isolated

External Load for I/O Interconnection

Not needed

Signal Determination Method

Static

Effect of Improper Input Connection

If any input exceeding the rated value is applied, permanent damage may be
caused.

Connector on Mother Board

MC1.5/11-G-3.81BK (Phoenix Contact)

Connector Insertion/Removal Durability

100 times minimum

Internal Current Draw

All Inputs ON

60 mA (5V DC)
0 mA (24V DC)

All Inputs OFF

30 mA (5V DC)
0 mA (24V DC)

Weight

80g

Input Internal Circuit

Input Usage Limits

When using the FC4A-N08A11, all inputs can be
turned on simultaneously at 55°C, input voltage
132V AC.

FC4A-N08A11

Input

Inter

nal Cir

cuit

COM

480 k

220

0.33 µF

Input V

oltage (V AC)

132

0

100

Input Simultaneous ON Ratio (%)

55°C

50

0

102

120

Input Operating Range

The input operating range of the Type 1, 2, 3 (IEC 61131-2)
input module is shown below:

FC4A-N08A11

74

20

0

1

Input Current (mA)

5

132

Input V

oltage (V AC)

2

4

17

79

Transition

OFF Area

ON Area

100

13

Area