IDEC MicroSmart User Manual

Page 130

Advertising
background image

5: S

PECIAL

F

UNCTIONS

5-10

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

Special Internal Relays for Single-phase High-speed Counters (Slim Type CPU Modules)

Note: Special internal relays M8130, M8131, M8133, M8134, M8135, and M8136 go on for only one scan.

Special Data Registers for Single-phase High-speed Counters (Slim Type CPU Modules)

Single-phase High-speed Counter Specifications (Slim Type CPU Modules)

Clearing High-speed Counter Current Value

The high-speed counter current value is reset to the reset value (two-phase high-speed counter) or to zero (single-phase
high-speed counters) in five ways:

• when the CPU is powered up,
• when a user program is downloaded to the CPU,
• when reset input I2 (HSC1) or I5 (HSC4 on slim type CPU only) is turned on,
• when current value overflow or underflow occurs (two-phase) or when the preset value is reached (single-phase), or
• when the reset input (not the high-speed counter reset input) designated in the Function Area Settings is turned on.

Precautions for Downloading High-speed Counter Program

When downloading a user program containing a high-speed counter, turn off the gate input before downloading the user
program.

If a user program containing a high-speed counter is downloaded while the gate input is on, the high-speed counter is dis-
abled. Then, to enable counting, stop and restart the

MicroSmart

. Or, turn off the gate input, and 3 scans later turn on the

gate input again. For ladder programs to delay the gate input 3 scans, see pages 5-16 and 5-17.

Description

High-speed Counter No.

ON

Read/Write

HSC1

HSC2

HSC3

HSC4

Comparison Output Reset

M8030

M8034

M8040

M8044

Turns off comparison output

R/W

Gate Input

M8031

M8035

M8041

M8045

Enables counting

R/W

Reset Input

M8032

M8036

M8042

M8046

Resets the current value

R/W

Reset Status

M8130

M8135

Current value reset by I2 or I5

Read only

Comparison ON Status

M8131

M8133

M8134

M8136

Preset value reached

Read only

Description

High-speed Counter No.

Updated

Read/Write

HSC1

HSC2

HSC3

HSC4

High-speed Counter Current Value

D8045

D8047

D8049

D8051

Ever y scan

Read only

High-speed Counter Preset Value

D8046

D8048

D8050

D8052

R/W

Maximum Counting Frequency

HSC1 and HSC4:

20 kHz

HSC2 and HSC3:

5 kHz

Counting Range

0 to 65535 (16 bits)

Operation Mode

Adding counter

Gate Control

Enable/disable counting

Current Value Reset

Current value is reset to 0 when the current value reaches the preset value, when
reset input I2 (HSC1) or I5 (HSC4), or when a reset input special internal relay is
turned on.

Status Relays

Special internal relays for indicating high-speed counter statuses.

Comparison Output

Any output number available on the CPU module can be designated as a comparison
output which turns on when the current value reaches the preset value.
Output numbers on expansion output or mixed I/O modules cannot be designated as a
comparison output.

Advertising