7: B

ASIC

I

NSTRUCTIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

7-23

MCS

and MCR

(Master Control Set and Reset)

The MCS (master control set) instruction is usually used in combination with the MCR (master control reset) instruction.
The MCS instruction can also be used with the END instruction, instead of the MCR instruction.

When the input preceding the MCS instruction is off, the MCS is executed so that all inputs to the portion between the
MCS and the MCR are forced off. When the input preceding the MCS instruction is on, the MCS is not executed so that
the program following it is executed according to the actual input statuses.

When the input condition to the MCS instruction is off and the MCS is executed, other instructions between the MCS and
MCR are executed as follows:

Input conditions cannot be set for the MCR instruction.

More than one MCS instruction can be used with one MCR instruction.

Corresponding MCS/MCR instructions cannot be nested within another pair of corresponding MCS/MCR instructions.

Instruction

Status

SOTU

Rising edges (ON pulses) are not detected.

SOTD

Falling edges (OFF pulses) are not detected.

OUT

All are turned off.

OUTN

All are turned on.

SET and RST

All are held in current status.

TML, TIM, TMH, and TMS

Current values are reset to zero.
Timeout statuses are turned off.

CNT, CDP, and CUD

Current values are held.
Pulse inputs are turned off.
Countout statuses are turned off.

SFR and SFRN

Shift register bit statuses are held.
Pulse inputs are turned off.
The output from the last bit is turned off.

Ladder Diagram

I0

I1

Input I0

ON

OFF

Input I1

ON

OFF

Output Q0

ON

OFF

Timing Chart

MCS

MCR

When input I0 is off, MCS is executed so that the subsequent
input is forced off.

When input I0 is on, MCS is not executed so that the following
program is executed according to the actual input statuses.

Instruction

Data

LOD
MCS
LOD
OUT
MCR

I0

I1
Q0

Program List

Q0