Troubleshooting Diagram 7

Does the monitored

input turn on and off?

NO

YES

NO

YES

YES

Call IDEC for assistance.

Monitor the designated stop or
reset input using WindLDR on a
computer.

NO

Is the designated stop or

reset input on?

Is M8000 off?

Turn on the designated input.

The input circuit in the CPU mod-
ule is damaged.
Replace the CPU module.

Is stop or

reset input designated in

the WindLDR Function Area

Settings?

Monitor the star t control special
internal relay M8000 using
WindLDR on a computer.

YES

Turn off the star t control special
internal relay M8000 using
WindLDR on a computer.

NO

Cannot stop or reset operation.

Note: To monitor M8000, from the WindLDR menu bar,
select Online > Monitor, then Online > Direct Monitor.
Enter M8000 in the Direct Monitor Dialog.

Note: To turn off M8000, from the WindLDR menu bar, select
Online > Monitor, then Online > Direct Set/Reset. Enter
M8000 in the Direct Set/Reset Dialog. Click Reset.