In the 1:1 computer link system, a computer can be connected to either port 1 or 2 on the

MicroSmart

CPU module. In the

1:N computer link system, a computer must be connected to port 2 on the CPU module and every CPU module must have
a unique device number 0 through 31. The Communication page in the Function Area Settings must be programmed for
each station in the computer link system. If required, communication parameters can also be changed.

Since these settings relate to the user program, the user program must be downloaded to the

MicroSmart

after changing

any of these settings.

1. From the

WindLDR

menu bar, select Configure > Function Area Settings. The Function Area Setting dialog box

appears.

2. Click the Communication tab, and select Maintenance Protocol in the Port 1 or 2 pull-down list.

3. Click the Configure button. The Communication Parameters dialog box appears. Change settings, if required.

4. Click the OK button.

Baud Rate (bps)

1200, 2400, 4800, 9600, 19200

Data Bits

7 or 8

Parity

None, Odd, Even

Stop Bits

1 or 2

Receive Timeout (ms)

10 to 2540 (10-msec increments)
(Receive timeout is disabled when 2550
is selected.)

Device Number

0 to 31

Mode Selection Input

Any input number

Note: Only when the mode selection input is turned on, the selected communication parameters are enabled.
Other wise, default communication parameters take effect; 9600 bps, 7 data bits, even parity, 1 stop bit,
receive timeout 500 msec.