AS-Interface Master Module

The AS-Interface master module can be used with FC4A-D20RK1, FC4A-D20RS1, FC4A-D40K3, and FC4A-D40S3
CPU modules to communicate digital data with slaves, such as sensor, actuator, and remote I/O data.

One AS-Interface master module can be used with one CPU module. The AS-Interface master module can connect a max-
imum of 62 digital I/O slaves. A maximum of seven analog I/O slaves can also be connected to the AS-Interface master
module (compliant with AS-Interface ver. 2.1 and analog slave profile 7.3).

AS-Interface Master Module Type Number

Parts Description

(1) LED Indicators

Status LEDs:

Indicate the AS-Interface bus status.

I/O LEDs:

Indicate the I/O status of the slave specified by the address LEDs.

Address LEDs:

Indicate slave addresses.

(2) Pushbuttons

Used to select slave addresses, change modes, and store configuration.

(3) AS-Interface Cable Terminal Block

Connects the AS-Interface cable.
One terminal block is supplied with the AS-Interface master module.
When ordering separately, specify Type No. FC4A-PMT3P and quantity
(package quantity: 2).

(4) AS-Interface Cable Connector

Installs the AS-Interface cable terminal block.

(5) Unlatch Button

Used to unlatch the AS-Interface master module from the CPU or I/O module.

(6) Expansion Connector

Connects to the CPU and other I/O modules.

(7) Module Label

Indicates the AS-Interface master module Type No. and specifications.

Module Name

Type No.

AS-Interface Master Module

FC4A-AS62M

(6) Expansion Connector

(7) Module Label

(1) LED Indicators

(4) AS-Inter face Cable Connector

(2) Pushbuttons

PB1
PB2

(5) Unlatch Button

(5) Unlatch Button

(3) AS-Inter face Cable Terminal Block

(supplied with the AS-Inter face master module)