Pid i, Nstruction, Fc4a m – IDEC MicroSmart User Manual

Page 371: Type k high alarm light output q1 heater, Fuse

Advertising
background image

21: PID I

NSTRUCTION

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

21-15

System Setup

Analog Input Data vs. Process Variable after Conversion

Temperature Control by Auto Tuning and PID Action

Type K

High Alarm Light

Output Q1

Heater

+24V

0V

10

11

12

13

14

15

DC OUT

COM

DC IN

0

1

2

3

4

5

6

7

L

N

100-240VAC

Ry.OUT
COM0

Ry.OUT
COM1

Ry.OUT
COM3 11

Ry.OUT
COM2 10

0

1

2

3

4

5

6

7

Fuse

+

+

L

Output Q0

IN0

FC4A-C24R2

FC4A-L03AP1

Thermocouple

High Alarm Value (S1+14): 2500 (250°C)

4095

Linear Conversion Minimum Value (S1+6): 0 (0°C)

Linear Conversion Maximum Value (S1+5): 13000 (1300°C)

Set Point (S3): 2000 (200°C)

AT Set Point (S1+21): 1500 (150°C)

Analog Input Data D760

Process Variable after Conversion (S1+0)

Process Variable before Conversion (S4)

0

Process Variable after Conversion (S1+0)

Time

High Alarm Value (S1+14): 2500 (250°C)

Set Point (S3): 2000 (200°C)

AT Set Point (S1+21): 1500 (150°C)

Auto Tuning

PID Action