Troubleshooting diagram 12 – IDEC MicroSmart User Manual

Page 499

Advertising
background image

29: T

ROUBLESHOOTING

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

29-19

Troubleshooting Diagram 12

Did you make

sure of source 1 operand of the

RXD instruction?

Call IDEC for assistance.

NO

Are communication

parameters set correctly

using WindLDR?

Are inputs to

more than 5 RXD instructions on

simultaneously?

Data is not received correctly
in the user communication mode.

Set the communication parameters
to match those of the remote termi-
nal using WindLDR (see page 17-5.)

Is the data register

designated as receive status

used repeatedly?

Correct the program to replace the
duplicate data register with a differ-
ent data register.

YES

NO

Is a star t delimiter

specified in the RXD

instruction?

YES

Did you check

the star t delimiter of incoming

data?

Did you check

the format of incoming

data?

Is an end delimiter

specified in the RXD

instruction?

Did you check

the end delimiter of

incoming data?

Is the receive

timeout value set correctly

using WindLDR?

Is one input

used to star t multiple RXD

instructions?

Make sure that the receive format
of the RXD instruction matches that
of the incoming data.

Correct the program to make
sure that inputs to more than 5
RXD instructions do not go on
simultaneously.

NO

YES

NO

YES

YES

YES

YES

YES

YES

NO

YES

NO

Use one input to star t one RXD
instruction without a star t delim-
iter.

Make sure that the star t delimiter
in the RXD instruction matches that
of the incoming data.

Make sure that the end delimiter
in the RXD instruction matches
that of the incoming data.

Make sure that the receive timeout
value is larger than character inter-
vals of the incoming data.

Make sure that the receive data
designated as the source 1 oper-
and is correct.

YES

NO

NO

NO

NO

NO