Special Data Registers for Error Information

Two data registers are assigned to store information on errors.

General Error Codes

The general error code is stored to special data register D8005 (general error code).

When monitoring the PLC status using

WindLDR

, the error code is displayed in the error code box under the Error Status in

the PLC Status dialog box using four hexadecimal digits 0 through F. Each digit of the error code indicates a different set
of conditions requiring attention. After the error code is cleared as described on the preceding page, the error code box is
left blank.

For example, the error code may read out “0021.” This indicates two conditions requiring attention, “User program sum
check error” from the third chart and “Power failure” from the fourth chart. If the read-out displays “000D,” this indicates
three conditions exist from only the fourth chart.

D8005

General Error Code

D8006

User Program Execution Error Code

Error Code: Most Significant Digit

F000 E000 D000 C000 B000 A000 9000 8000 7000 6000 5000 4000 3000 2000 1000 0000

I/O bus initialize error

X

Error Code: 2nd Digit from Left

F00

E00

D00

C00

B00

A00

900

800

700

600

500

400

300

200

100

000

User program writing error

X

X

X

X

X

X

X

X

CPU module error

X

X

X

X

X

X

X

X

Clock IC error

X

X

X

X

X

X

X

X

Error Code: 3rd Digit from Left

F0

E0

D0

C0

B0

A0

90

80

70

60

50

40

30

20

10

00

TIM/CNT preset value sum check error

X

X

X

X

X

X

X

X

User program RAM sum check error

X

X

X

X

X

X

X

X

Keep data error

X

X

X

X

X

X

X

X

User program syntax error

X

X

X

X

X

X

X

X

Error Code: Least Significant Digit

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

Power failure

X

X

X

X

X

X

X

X

Watchdog timer error

X

X

X

X

X

X

X

X

Data link connection error

X

X

X

X

X

X

X

X

User program EEPROM sum check error

X

X

X

X

X

X

X

X