Alt (alternate output), Alt (alternate output) -14 – IDEC MicroSmart User Manual

Page 266

Advertising
background image

14: D

ATA

C

ONVERSION

I

NSTRUCTIONS

14-14

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

ALT (Alternate Output)

Applicable CPU Modules

Valid Operands

For the valid operand number range, see pages 6-1 and 6-2.

Since the ALT instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction must
be used.

Example: ALT

FC4A-C10R2/C

FC4A-C16R2/C

FC4A-C24R2/C

FC4A-D20K3/S3

FC4A-D20RK1/RS1 & FC4A-D40K3/S3

X

Operand

Function

I

Q

M

R

T

C

D

Constant

Repeat

D1 (Destination 1)

Bit to turn on and off

X

X

X

When input is turned on, output, internal relay, or shift register bit designated by
D1 is turned on and remains on after the input is turned off.

When input is turned on again, the designated output, internal relay, or shift reg-
ister bit is turned off.

The ALT instruction must be used with a SOTU or SOTD instruction, other wise the
designated output, internal relay, or shift register bit repeats to turn on and off in
each scan.

ALT

D1

*****

SOTU

D1
Q0

I0

ALT

When input I0 is turned on, output Q0 designated by operand D1 is turned on and
remains after input I0 is turned off.

When input I0 is turned on again, output Q0 is turned off.

SOTU

Input I0

Output Q0

ON

OFF

ON

OFF