Selection of HMI Module Initial Screen

Special data register D8068 is available on upgraded CPU modules with system program version shown in the table below.
For the procedure to confirm the system program version of the CPU module, see page 29-1.

D8068 can be used to select the initial screen display of the HMI module when the CPU module is powered up.

When a keep data error occurs, mode 1 is enabled regardless of the value stored in data register D8068.

Key Operation for Selecting Operand Number

When the OK button is pressed while a menu screen is shown, the screen switches to the control screen of the menu. For
example, while the timer menu is on the display, pressing the OK button switches the screen to the timer control screen,
where operand numbers and values are selected. For operation examples, see the following pages.

CPU Module

All-in-One Type

Slim Type

FC4A-C10R2
FC4A-C10R2C

FC4A-C16R2
FC4A-C16R2C

FC4A-C24R2
FC4A-C24R2C

FC4A-D20K3
FC4A-D20S3

FC4A-D20RK1
FC4A-D20RS1
FC4A-D40K3
FC4A-D40S3

System Program Version

203 or higher

202 or higher

202 or higher

202 or higher

201 or higher

Data Register

Value

Description

D8068

0, 2 through 65535

Mode 1: Indicates the PLC program version each time the PLC is powered up.

1

Mode 2: Indicates the same menu as when the PLC was shut down.

OK Switches to the control screen.

Slow Flashing

ESC Discards the changes and
returns to the menu screen.

▲ Shifts up one digit.

▼ Decrements the number.

▼ Shifts down one digit.

▲ Increments the number.

OK Saves the changes and goes to the next screen.

Fast Flashing

OK Selects the digit and changes to fast flashing.

ESC Returns to slow flashing.

ESC Returns to fast flashing.