Using WindLDR

This section describes the procedures to use

WindLDR

for the AS-Interface system.

WindLDR

contains the Configure AS-

Interface Master dialog box to configure slaves and to change slave addresses, and the Monitor AS-Interface Slave dialog
box to monitor the slave operation.

For the procedures to select the PLC type and Function Area Settings, see page 28-8.

Configure AS-Interface Master

AS-Interface compatible slave devices are set to address 0 at factory and must be assigned a unique slave address so that
the master can communicate with the slave correctly.

From the

WindLDR

menu bar, select

Configure

>

AS-Interface Master

. The Configure AS-Interface Master dialog box

appears.

Dialog Box

Button

Description

Configure AS-Interface
Master

Auto Configuration

Writes the currently connected AS-Inter face slave configuration
(LDS, CDI, PI) information to the AS-Inter face master module
EEPROM (LPS, PCD, PP).

Manual Configuration

Writes the slave PCD and parameters configured by the user to the
AS-Inter face master module EEPROM (LPS, PCD, PP).

Refresh

Refreshes the screen display.

Switch Slave

Switches the dialog box for setting Slave A or Slave B.

File Open

Opens the configuration (LPS, PCD, PP) file.

File Save

Saves the configuration (LPS, PCD, PP) file.

Help

Displays explanations for functions on the screen.

Change Slave Address

OK

Changes the slave address.

Cancel

Discards the changes and closes the window.

Configure Slave

OK

Updates the PCD and PP. Not written to the master module yet.

Cancel

Discards the changes and closes the window.

Click the slave address to
open the Change Slave
Address dialog box.

Click a PCD value to
open the Configure
Slave dialog box.