Two-phase High-speed Counter Timing Chart

Example: Reset input I2 is used. Q1 is designated as a comparison output.

Reset Input I2

Reset Value D8046

0

1

2

8

Current Value D8045

1 scan time

The D8046 value at this point becomes the
reset value for the next counting cycle.

Phase A Input I0

Phase B Input I1

65533

5

Reset Status M8130

3

Gate Input M8031

Comparison Output Q1

Comparison Output Reset M8030

1 scan time

Current Value Over flow M8131

1 scan time

Current Value Under flow M8132

7
6
5
4
3

65532

65533

65534

65535

Under flow

Over flow

• When reset input I2 is turned on, the D8046 reset value is set to the D8045 current value, then reset status

M8130 turns on for one scan. If reset input M8032 is turned on, reset status M8130 does not turn on.

• While gate input M8031 is on, the two-phase high-speed counter counts up or down depending on the phase dif-

ference between phase A (input I0) and phase B (input I1).