Data Link System Setup

To set up a data link system, install the RS485 communication adapter (FC4A-PC3) to the port 2 connector on the all-in-
one 16- or 24-I/O type CPU module.

When using the slim type CPU module, mount the RS485 communication module (FC4A-HPC3) next to the CPU module.

When using the optional HMI module with the slim type CPU module (not shown below), install the RS485 communica-
tion adapter (FC4A-PC3) to the port 2 connector on the HMI base module.

Connect the RS485 terminals A, B, and SG on every CPU module using a shielded twisted pair cable as shown below. The
total length of the cable for the data link system can be extended up to 200 meters (656 feet).

A B SG

Cable

Cable

A B SG

Master Station

Slave Station 1

Slave Station 2

Slave Station 31

RS485 Communication

Adapter FC4A-PC3

on Por t 2 Connector

RS485 Communication

Module FC4A-HPC3

Por t 2

All-in-One Type
CPU Module

Slim Type
CPU Module

Shielded twisted pair cable 200 meters (656 feet) maximum

Core wire 0.3mm

2