Troubleshooting diagram 4 – IDEC MicroSmart User Manual

Page 491

Advertising
background image

29: T

ROUBLESHOOTING

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

29-11

Troubleshooting Diagram 4

Are wiring and

operation of external

devices correct?

Is the input terminal

powered correctly?

Is the input wiring correct?

Input does not operate normally.

END

YES

NO

Are input allocation

numbers correct?

Call IDEC for assistance.

Correct the external
device wiring.

Is the input LED on?

Correct the program.

YES

NO

NO

YES

NO

YES

YES

NO

Correct the input
wiring.

Supply the rated voltage to the
input terminal.

Input voltage range
All-in-one CPU, input, mixed I/O modules: 20.4 to 28.8V DC
Slim type CPU modules:

20.4 to 26.4V DC

AC input module:

85 to 132V AC

Advertising