PECIFICATIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

2-49

Note 1: Total input system transfer time = Sample repetition time + Internal processing time
The total input system transfer time increases in propor tion to the number of channels used.

Note 2: The data processed in the analog I/O module can be linear-conver ted to a value between –32768 and 32767. The
optional range designation, and analog I/O data minimum and maximum values can be selected using data registers allo-
cated to analog I/O modules. See page 24-12.

Note 3: When an error is detected, a corresponding error code is stored to a data register allocated to analog I/O operating
status. See page 24-6.

Data

Digital Resolution

50000 increments (16 bits)

K:

Approx.

24000 increments
(15 bits)

J:

Approx.

33000 increments
(15 bits)

T:

Approx.

10000 increments
(14 bits)

Pt100:

Approx.

6400 increments
(13 bits)

Pt1000:

Approx.

64000 increments
(16 bits)

Ni100:

Approx.

4700 increments
(13 bits)

Ni1000:

Approx.

47000 increments
(16 bits)

Input Value of LSB

0.2 mV

0.32 µA

K: 0.058°C
J: 0.038°C
T: 0.042°C

Pt100:

0.086°C

Pt1000:

0.0086°C

Ni100:

0.037°C

Ni1000:

0.0037°C

Data Type in Application
Program

Default:

0 to 50000

Default:
0 to 50000

Pt100, Ni100:
0 to 6000

Pt1000, Ni1000:
0 to 60000

Optional: –32768 to 32767 (selectable for each channel) (Note 2)

Temperature: Celsius, Fahrenheit

Monotonicity

Yes

Input Data Out of Range

Detectable (Note 3)

Noise
Resistance

Maximum Temporary
Deviation during
Electrical Noise Tests

±3% maximum
(when a 500V clamp voltage is applied to the power sup-
ply and I/O lines)

Not assured

Input Filter

Software

Recommended Cable for
Noise Immunity

Twisted pair cable

Crosstalk

2 LSB maximum

Isolation

Between input and power circuit:

Isolated

Between input and internal circuit:

Photocoupler-isolated

Effect of Improper Input Connection

No damage

Maximum Permanent Allowed Overload
(No Damage)

11V DC

22 mA DC

Selection of Analog Input Signal Type

Using programming software

Calibration or Verification to Maintain
Rated Accuracy

Not possible

Type No.

FC4A-J4CN1 / FC4A-J8C1

FC4A-J4CN1

Analog Input Signal Type

Voltage Input

Current Input

Thermocouple

Resistance

Thermometer

Advertising