IDEC MicroSmart User Manual

Page 69

Advertising
background image

2: M

ODULE

S

PECIFICATIONS

« FC4A M

ICRO

S

MART

U

SER

’

S

M

ANUAL

»

2-49

Note 1: Total input system transfer time = Sample repetition time + Internal processing time
The total input system transfer time increases in propor tion to the number of channels used.

Note 2: The data processed in the analog I/O module can be linear-conver ted to a value between –32768 and 32767. The
optional range designation, and analog I/O data minimum and maximum values can be selected using data registers allo-
cated to analog I/O modules. See page 24-12.

Note 3: When an error is detected, a corresponding error code is stored to a data register allocated to analog I/O operating
status. See page 24-6.

Data

Digital Resolution

50000 increments (16 bits)

K:

Approx.

24000 increments
(15 bits)

J:

Approx.

33000 increments
(15 bits)

T:

Approx.

10000 increments
(14 bits)

Pt100:

Approx.

6400 increments
(13 bits)

Pt1000:

Approx.

64000 increments
(16 bits)

Ni100:

Approx.

4700 increments
(13 bits)

Ni1000:

Approx.

47000 increments
(16 bits)

Input Value of LSB

0.2 mV

0.32 µA

K: 0.058°C
J: 0.038°C
T: 0.042°C

Pt100:

0.086°C

Pt1000:

0.0086°C

Ni100:

0.037°C

Ni1000:

0.0037°C

Data Type in Application
Program

Default:

0 to 50000

Default:
0 to 50000

Pt100, Ni100:
0 to 6000

Pt1000, Ni1000:
0 to 60000

Optional: –32768 to 32767 (selectable for each channel) (Note 2)

—

Temperature: Celsius, Fahrenheit

Monotonicity

Yes

Input Data Out of Range

Detectable (Note 3)

Noise
Resistance

Maximum Temporary
Deviation during
Electrical Noise Tests

±3% maximum
(when a 500V clamp voltage is applied to the power sup-
ply and I/O lines)

Not assured

Input Filter

Software

Recommended Cable for
Noise Immunity

Twisted pair cable

—

Crosstalk

2 LSB maximum

Isolation

Between input and power circuit:

Isolated

Between input and internal circuit:

Photocoupler-isolated

Effect of Improper Input Connection

No damage

Maximum Permanent Allowed Overload
(No Damage)

11V DC

22 mA DC

—

Selection of Analog Input Signal Type

Using programming software

Calibration or Verification to Maintain
Rated Accuracy

Not possible

Type No.

FC4A-J4CN1 / FC4A-J8C1

FC4A-J4CN1

Analog Input Signal Type

Voltage Input

Current Input

Thermocouple

Resistance

Thermometer

Advertising