Start/Stop Operation

This section describes operations to start and stop the

MicroSmart

and to use the stop and reset inputs.

Start/Stop Schematic

The start/stop circuit of the

MicroSmart

consists of

three blocks; power supply, M8000 (start control spe-
cial internal relay), and stop/reset inputs. Each block
can be used to start and stop the

MicroSmart

while

the other two blocks are set to run the

MicroSmart

.

Start/Stop Operation Using WindLDR

The

MicroSmart

can be started and stopped using

WindLDR

run on a Windows PC connected to the

MicroSmart

CPU

module. When the PLC Start button is pressed in the dialog box shown below, start control special internal relay M8000
is turned on to start the

MicroSmart

. When the PLC Stop button is pressed, M8000 is turned off to stop the

MicroSmart

.

1. Connect the PC to the

MicroSmart

, start

WindLDR

, and power up the

MicroSmart

. See page 4-1.

2. Check that a stop input is not designated using Configure > Function Area Settings > Run/Stop. See page 5-2.

Note: When a stop input is designated, the

MicroSmart

cannot be star ted or stopped by turning star t control special inter-

nal relay M8000 on or off.

3. Select Online from the

WindLDR

menu bar, then select Download Program. Or, click the download icon

.

The Download Program dialog box appears.

4. Click the PLC Start button to start operation, then the start control special internal relay M8000 is turned on.

5. Click the PLC Stop button to stop operation, then the start control special internal relay M8000 is turned off.

The PLC operation can also be started and stopped while

WindLDR

is in the monitor mode. To access the Start or Stop

button, select Online > Monitor and select Online > PLC Status > Run/Stop Status.

Note: Special internal relay M8000 is a keep type internal relay and stores the status when power is turned off. M8000
retains its previous status when power is turned on again. However, when the backup batter y is dead, M8000 loses the
stored status, and can be turned on or off as programmed when the

MicroSmart

is powered up. The selection is made in

Configure > Function Area Settings > Run/Stop > Run/Stop Selection at Memory Backup Error. See page 5-3.

The backup duration is approximately 30 days (typical) at 25°C after the backup battery is fully charged.

• Make sure of safety before starting and stopping the

MicroSmart

. Incorrect operation on the

MicroSmart

may cause machine damage or accidents.

Caution

Power
Supply

M8000

Stop

Input

Reset

Input

Star t

Star t Control

PLC

WindLDR