15: W

EEK

P

ROGRAMMER

I

NSTRUCTIONS

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

15-5

Setting Calendar/Clock Using WindLDR

Before using the clock cartridge for the first time, the calendar/clock data in the clock cartridge must be set using

WindLDR

or executing a user program to transfer correct calendar/clock data from special data registers allocated to the calendar/
clock. Once the calendar/clock data is stored, the data is held by the backup battery in the clock cartridge.

1. Select Online from the

WindLDR

menu bar, then select Monitor. The screen display changes to the monitor window.

2. From the Online menu, select PLC Status. The MicroSmart PLC Status dialog box is displayed. The current calendar/

clock data is read out from the clock cartridge and displayed in the Calendar box.

3. Click the Change button in the Calendar box. The Set Calendar and Time dialog box comes up with the date and time

values read from the computer internal clock.

4. Click the Down Arrow button on the right of Calendar, then a calendar is displayed where you can change the year,

month, and date. Enter or select new values.

5. To change hours and minutes, click in the Time box, and type a new value or use the up/down keys. When new values

are entered, click the OK button to transfer the new values to the clock cartridge.

Setting Calendar/Clock Using a User Program

Another way of setting the calendar/clock data is to store the values in special data registers dedicated to the calendar and
clock and to turn on special internal relay M8016, M8017, or M8020. Data registers D8015 through D8021 do not hold the
current values of the calendar/clock data but hold unknown values before executing a user program.

Special Data Registers for Calendar/Clock Data

Note: The day of week value is assigned for both current and new data as follows:

Data Register No.

Data

Value

Read/Write

Updated

D8008

Year (current data)

0 to 99

Read only

500 ms or one scan time
whichever is larger

D8009

Month (current data)

1 to 12

D8010

Day (current data)

1 to 31

D8011

Day of week (current data)

0 to 6 (Note)

D8012

Hour (current data)

0 to 23

D8013

Minute (current data)

0 to 59

D8014

Second (current data)

0 to 59

D8015

Year (new data)

0 to 99

Write only

Not updated

D8016

Month (new data)

1 to 12

D8017

Day (new data)

1 to 31

D8018

Day of week (new data)

0 to 6 (Note)

D8019

Hour (new data)

0 to 23

D8020

Minute (new data)

0 to 59

D8021

Second (new data)

0 to 59

0

1

2

3

4

5

6

Sunday

Monday

Tuesday

Wednesday

Thursday

Friday

Saturday