Special Internal Relays for Data Link Communication

Special internal relays M8005 through M8007 and M8080 through M8117 are assigned for the data link communication.

M8005 Data Link Communication Error

When an error occurs during communication in the data link system, M8005 turns on. The M8005 status is maintained
when the error is cleared and remains on until M8005 is reset using

WindLDR

or until the CPU is turned off. The cause of

the data link communication error can be checked using Online > Monitor, followed by Online > PLC Status > Error
Status: Details
. See page 25-4.

M8006 Data Link Communication Prohibit Flag (Master Station)

When M8006 at the master station is turned on in the data link system, data link communication is stopped. When M8006
is turned off, data link communication resumes. The M8006 status is maintained when the CPU is turned off and remains
on until M8006 is reset using

WindLDR

.

When M8006 is on at the master station, M8007 is turned on at slave stations in the data link system.

M8007 Data Link Communication Initialize Flag (Master Station)

Data Link Communication Stop Flag (Slave Station)

M8007 has a different function at the master or slave station of the data link communication system.

Master station: Data link communication initialize flag

When M8007 at the master station is turned on during operation, the link configuration is checked to initialize the data link
system. When a slave station is powered up after the master station, turn M8007 on to initialize the data link system. After
a data link system setup is changed, M8007 must also be turned on to ensure correct communication.

Slave station: Data link communication stop flag

When a slave station does not receive communication data from the master station for 10 seconds or more in the data link
system, M8007 turns on. When a slave station does not receive data in 10 seconds after initializing the data link system,
M8007 also turns on at the slave station. When the slave station receives correct communication data, M8007 turns off.

M8080-M8116 Slave Station Communication Completion Relay (Master Station)

Special internal relays M8080 through M8116 are used to indicate the completion of data refresh. When data link commu-
nication with a slave station is complete, a special internal relay assigned for the slave station is turned on for one scan
time at the master station.

M8080 Communication Completion Relay (Slave Station)

When data link communication with a master station is complete, special internal relay M8080 at the slave station is
turned on for one scan time.

M8117 All Slave Station Communication Completion Relay

When data link communication with all slave stations is complete, special internal relay M8117 at the master station is
turned on for one scan time. M8117 at slave stations does not go on.

Special Internal

Relay

Slave Station

Number

Special Internal

Relay

Slave Station

Number

Special Internal

Relay

Slave Station

Number

M8080

Slave Station 1

M8092

Slave Station 11

M8104

Slave Station 21

M8081

Slave Station 2

M8093

Slave Station 12

M8105

Slave Station 22

M8082

Slave Station 3

M8094

Slave Station 13

M8106

Slave Station 23

M8083

Slave Station 4

M8095

Slave Station 14

M8107

Slave Station 24

M8084

Slave Station 5

M8096

Slave Station 15

M8110

Slave Station 25

M8085

Slave Station 6

M8097

Slave Station 16

M8111

Slave Station 26

M8086

Slave Station 7

M8100

Slave Station 17

M8112

Slave Station 27

M8087

Slave Station 8

M8101

Slave Station 18

M8113

Slave Station 28

M8090

Slave Station 9

M8102

Slave Station 19

M8114

Slave Station 29

M8091

Slave Station 10

M8103

Slave Station 20

M8115

Slave Station 30

M8116

Slave Station 31