CDP (Dual-Pulse Reversible Counter)

The dual-pulse reversible counter CDP has up and down pulse inputs, so that three inputs are required. The circuit for a
dual-pulse reversible counter must be programmed in the following order: preset input, up-pulse input, down-pulse input,
the CDP instruction, and a counter number C0 through C99, followed by a counter preset value from 0 to 65535.

The preset value can be designated using a decimal constant or a data register. When a data register is used, the data of the
data register becomes the preset value.

500 500

Ladder Diagram

Preset Input I0

ON

OFF

Up Pulse I1

ON

OFF

Down Pulse I2

ON

OFF

Timing Chart

Counter C1

ON

OFF

500 501 502 501

Counter C1 Value

500 499

0

1

• • •

• • •

I0

I1

CDP

C1

500

I2

Preset Input

Up Pulse

Down Pulse

I3

C1

Instruction

Data

LOD
LOD
LOD
CDP

LOD
AND
OUT

I0
I1
I2
C1
500
I3
C1
Q1

Program List

• The same counter number cannot be pro-

grammed more than once.

• The preset input must be turned on initially so

that the current value returns to the preset
value.

• The preset input must be turned off before

counting may begin.

• When the up pulse and down pulses are on

simultaneously, no pulse is counted.

• The counter output is on only when the cur-

rent value is 0.

• After the current value reaches 0 (counting

down), it changes to 65535 on the next count
down.

• After the current value reaches 65535 (count-

ing up), it changes to 0 on the next count up.

• When power is off, the counter’s current

value is held, and can also be designated as
“clear” type counters using the Function Area
Settings (see page 5-4).

• Counter preset and current values can be

changed using

WindLDR

without download-

ing the entire program to the CPU again.
From the

WindLDR

menu bar, select Online >

Monitor, then select Online > Point Write.
To change a counter preset value, specify the
counter number with a capital C and a new
preset value. To change a counter current
value, specify the counter number with a
small c and a new current value while the
counter preset input is off.

• When the preset or current value is changed

during counter operation, the change
becomes effective immediately.

• For the data movement when changing, con-

firming, and clearing preset values, see page
7-13. Preset v
alues can also be changed and
changed preset values can be confirmed using
the HMI module. See pages 5-35 and 5-36.

Q1

Caution

• For restrictions on ladder programming

of counter instructions, see page 29-22.