IDEC MicroSmart User Manual

Page 413

Advertising
background image

25: D

ATA

L

INK

C

OMMUNICATION

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

25-5

Data Link Communication between Master and Slave Stations

The master station has 6 data registers assigned to transmit data to a slave station and 6 data registers assigned to receive
data from a slave station. The quantity of data registers for data link can be selected from 0 through 6 using

WindLDR

. The

following examples illustrate how data is exchanged between the master and slave stations when 2 or 6 data registers are
used for data link communication with each of 31 slave stations.

Example 1: Transmit Data 2 Words and Receive Data 2 Words

Example 2: Transmit Data 6 Words and Receive Data 6 Words

Master Station

D8069

Communication Error

D900 - D901

Transmit Data

D906 - D907

Receive Data

D8070

Communication Error

D912 - D913

Transmit Data

D918 - D919

Receive Data

D8071

Communication Error

D924 - D925

Transmit Data

D930 - D931

Receive Data

D8072

Communication Error

D936 - D937

Transmit Data

D942 - D943

Receive Data

D8098

Communication Error

D1248 - D1249

Transmit Data

D1254 - D1255

Receive Data

D8099

Communication Error

D1260 - D1261

Transmit Data

D1266 - D1267

Receive Data

Slave Stations

D8069

Communication Error

Slave Station 1

D900 - D901

Transmit Data

D906 - D907

Receive Data

D8069

Communication Error

Slave Station 2

D900 - D901

Transmit Data

D906 - D907

Receive Data

D8069

Communication Error

Slave Station 3

D900 - D901

Transmit Data

D906 - D907

Receive Data

D8069

Communication Error

Slave Station 4

D900 - D901

Transmit Data

D906 - D907

Receive Data

D8069

Communication Error

Slave Station 30

D900 - D901

Transmit Data

D906 - D907

Receive Data

D8069

Communication Error

Slave Station 31

D900 - D901

Transmit Data

D906 - D907

Receive Data

Master Station

D8069

Communication Error

D900 - D905

Transmit Data

D906 - D911

Receive Data

D8070

Communication Error

D912 - D917

Transmit Data

D918 - D923

Receive Data

D8071

Communication Error

D924 - D929

Transmit Data

D930 - D935

Receive Data

D8072

Communication Error

D936 - D941

Transmit Data

D942 - D947

Receive Data

D8098

Communication Error

D1248 - D1253

Transmit Data

D1254 - D1259

Receive Data

D8099

Communication Error

D1260 - D1265

Transmit Data

D1266 - D1271

Receive Data

Slave Stations

D8069

Communication Error

Slave Station 1

D900 - D905

Transmit Data

D906 - D911

Receive Data

D8069

Communication Error

Slave Station 2

D900 - D905

Transmit Data

D906 - D911

Receive Data

D8069

Communication Error

Slave Station 3

D900 - D905

Transmit Data

D906 - D911

Receive Data

D8069

Communication Error

Slave Station 4

D900 - D905

Transmit Data

D906 - D911

Receive Data

D8069

Communication Error

Slave Station 30

D900 - D905

Transmit Data

D906 - D911

Receive Data

D8069

Communication Error

Slave Station 31

D900 - D905

Transmit Data

D906 - D911

Receive Data

Advertising