IDEC MicroSmart User Manual

Page 332

Advertising
background image

20: P

ULSE

I

NSTRUCTIONS

20-4

« FC4A M

ICRO

S

MART

U

SER

S

M

ANUAL

»

D1+1 Pulse Output Complete

The internal relay designated by operand D1+1 turns on when the PULS1 instruction has completed generating a predeter-
mined number of output pulses or when either PULS instruction is stopped to generate output pulses. When the start input
for the PULS instruction is turned on, the internal relay designated by operand D1+1 turns off.

D1+2 Pulse Output Overflow

The internal relay designated by operand D1+2 turns on when the PULS1 instruction has generated more than the prede-
termined number of output pulses. When the start input for the PULS instruction is turned on, the internal relay designated
by operand D1+2 turns off.

Special Data Register for Pulse Outputs

Upgraded CPU modules have two additional special data registers to store the current frequency of pulse outputs.

Timing Chart for Enable Pulse Counting

This program demonstrates a timing chart of the PULS1 instruction when pulse counting is enabled.

Allocation No.

Function

Description

D8055

Current Pulse Frequency
of PULS1 or RAMP (Q0)

While the PULS1 or RAMP instruction is executed, D8055 stores the cur-
rent pulse frequency of output Q0.
The value is updated ever y scan.

D8056

Current Pulse Frequency
of PULS2 or RAMP (Q1)

While the PULS2 or RAMP (reversible control dual-pulse output) instruction
is executed, D8056 stores the current pulse frequency of output Q1.
The value is updated ever y scan.

D1

M50

I0

PULS
1

S1

D200

D202 = 1 (enable pulse counting)

Output Pulse Q0

Output Pulse Frequency D201

PV1

FR1

Star t Input I0

• When input I0 is turned on, PULS1 star ts to generate output pulses at the frequency designated by the value

stored in data register D201. While the output pulses are sent out from output Q0, internal relay M50 remains on.

• When the quantity of generated output pulses reaches the preset value designated by data registers D203 and

D204, PULS1 stops generating output pulses. Then internal relay M50 turns off, and internal relay M51 turns on.

• If the output pulse frequency value in D201 is changed while generating output pulses, the change takes effect in

the next scan. When changing the pulse frequency, make sure that the timing of the change is much slower than
the output pulse frequency, so that the pulse frequency is changed successfully.

• If input I0 is turned off before reaching the preset value, PULS1 stops generating output pulses immediately, then

internal relay M50 turns off and internal relay M51 turns on.

FR2

FR3

Preset Value D203·D204

PV1

PV2

PV3

Pulse Output ON M50

Pulse Output Complete M51

PV2