Event Processor

Setting event conditions

5. Click the “Conditions” tab to display the “Event Condition Page.”

6. Even if a specified event condition is matched, the event only occurs if you enable

the function by selecting the Continue check box.

• When selected: Continue judging conditions even after first match.
• When cleared: Discontinue after matching the condition once.

7. The “Logic” list box is used to specify “AND” or “OR” when specifying the relationship

between two types of conditions.

8. Select the condition from “Alarm,” “Time,” “System,” and “Value” in the “Condition

Type” list box.

9. For each condition type, set as follows:

• When set to Alarm

The event is executed at the time when the specified alarm condition is met.

The condition is determined only when scanning is in progress.

Select the tag of the alarm you wish to detect.

Click All Groups or All Tags button to display the Group

Selection or Tag Selection dialog box.

Select the alarm you wish to detect.

Select the Alarm Status from “Changed”, “OFF -> ON”, and “ON-> OFF.”