Alarm action
• No Logging

Select [ON] to hide alarm indication. The [Detect] setting is enabled in the Measure

channel, Math channel, Ext channel tab(s).

This function disables the alarm indicator and the logging of alarm events to the alarm

summary. It also disables the display of alarms by the alarm annunciator (release

number 3 or later).

• Annunciator mode and Sequence (Release number 3 or later)

To use the annunciator function, select [ON] and set the sequence.

Settings

Description

ISA-A-4

A no lock-in sequence.

ISA-A

A lock-in sequence.

ISA-M

A double lock-in sequence.

• Time off color (Release number 3 or later)

The annunciator window display color when no alarms are activated. You can select

[White] or [Green].

Alarm display (Release number 3 or later)
• Level

When multiple alarms occur, the DX gives higher priority to the display of alarms with

higher levels.

Settings

Description

1>2>3>4

The order of alarm level preference, from highest to lowest preference, is 1, 2,
3, 4.

1>4>2>3

The order of alarm level preference, from highest to lowest preference, is 1, 4,
2, 3.

1>4>3>2

The order of alarm level preference, from highest to lowest preference, is 1, 4,
3, 2.

• Alarm 1, Alarm 2, Alarm 3, and Alarm 4

You can set the alarm color for each alarm level. It is easy to understand what

processes are taking place when alarms occur if you associate an alarm’s color with

its level. This setting applies to all channels.