Yokogawa DAQWORX User Manual

Page 332

Advertising
background image

7-156

IM WX101-01E

7.8 Setting MV1000/MV2000

• Start channel/End channel (client channels)

Enter the first and last channel numbers of input/output. The range of channels that

you can enter varies depending on the command type as follows:

Read: 201 to 440, R-Math: C01 to C60, Write: 1 to 48, W-Math: 101 to 160

• Connected to (server number)

Select the server number from 1 to 16.

• Register

Set the register number of the server.

For an input register, select in the range of 30001 to 39999 and 300001 to 365536.

For a hold register, select in the range of 40001 to 49999 and 400001 to 465536.

The register numbers you can specify vary depending on the command type. See

section 6/3 of the MV1000/MV2000 Communication Interface User’s Manual (IM

MV1000-17E).

• Type

Select INT16, UINT16, INT32_B, INT32_L, UINT32_B, UINT32_L, FLOAT_B, or

FLOAT_L.

The register numbers you can specify vary depending on the command type. See

section 6.3 of the MV1000/MV2000 Communication Interface User’s Manual (IM

MV1000-17E).

E-mail

Basic Setting

Set the SMTP server and mail address.

• SMTP server name

Enter the host name or IP address of the SMTP server.

• Port No.

Unless specified otherwise, set the number to the default value. The default value is 25.