Setting the Recorder

• Wait action

Set the wait action type to [Shift] or [Within]. To disable the wait action, select [Off].

• Wait zone number

Select the wait zone number from [1] to [5]. This item is available only when [Wait

action] is set to [Shift] or [Within].

PV Event

Set the PV Event.

Click this tab

PV event display

• Loop

Set the target loop number [1] to [6] of the PV event (only selectable loop numbers).

Up to 16 events can be assigned. Select [Off] (initial setting) for the number of the

loops to which the event is not to be assigned.

• Type

Select the type of PV event from the following.

PV high-limit, PV low-limit, deviation high-limit, deviation low-limit, deviation high & low

limit, deviation within high & low limits, SP high-limit, SP low-limit , output high-limit ,

and output low-limit

• Value

Set the value in the following range according to the type of PV event.

PV/SP event: EU (0.0 to 100.0%) of the measurement span

Deviation high-limit event/low-limit event: EUS (–100.0 to 100.0%) of the measurement

span

Deviation high & low limit/within high & low limits: EUS (0.0 to 100.0%) of the

measurement span

Output event: –5.0% to 105.0% of the output

PV event display

A bar showing that the PV event was set is displayed in the upper part of the program

pattern screen display screen.

7.10 Setting CX Series