Index – Yokogawa DAQWORX User Manual

Page 297

Advertising
background image

7-121

IM WX101-01E

1

2

3

4

5

6

7

8

9

Index

Setting the Recorder

7.8 Setting MV1000/MV2000

Alarm

Four alarms (Alarm 1 to 4) can be specified on each channel.

Type

Select H, L, h, l, R, r, T or t. The selectable alarms vary depending on the input mode

and computation type. For details, see chapter 3 in the MV1000/MV2000 User’s Manual

(IM MV1000-01E).

Alarm value

Alarm is generated using the specified value as the boundary. The selectable range of

alarm values vary depending on the input mode and range.

Alarm delay

Set the alarm delay time to an integer between 1 and 3600 seconds.

Alarm is generated when the measured value stays above or below the specified alarm

value for the specified time (delay period).

Note

MV1000/MV2000 specifications
• The alarm delay time takes on a value that is an integer multiple of the scan interval. For

example, if the alarm delay time is set to 5 s when the scan interval is 2 s, the actual delay

time is 6 s.

• The delay alarm has the following special operations.

• If the computation is stopped in a condition in which the computed value is exceeding the

alarm setting when a delay alarm is set on a computation channel, the alarm is turned On

after the specified period (delay period) elapses.

• The alarm detection operation is reset if a power failure occurs. The operation restarts after

the power recovers.

• If the alarm setting of the delay high limit alarm is changed when an alarm is already

activated and the input is greater than or equal to the new setting, the alarm continues. For

all other cases, the alarm detection operation starts at the new setting. This is also true for

the delay lower limit alarm.

Alarm Relay

To output relays, select the output relay number. Otherwise, select [None].

Detect

This can be selected when [Alarm No Logging] is turned [ON] under [Detail Setting] in

the [Basic Setting] tab.

Select whether to show or hide the alarm indication when an alarm occurs. If set to [OFF],

a signal is output to the alarm output relay or internal switch when an alarm occurs, but it

is not indicated on the screen. The alarm is also not recorded in the alarm summary.

Moving Average

To use the moving average, select the sampling count [Times] (2 to 400).

Tag

Up to 16 characters can be entered for the tag.

You can use the tag name instead of the channel number to be displayed on the screen.

This can be selected when [Tag] is [Tag] under [Detail Setting] in the [Basic Setting] tab.

Advertising
This manual is related to the following products: