Setting the Recorder

Option

• Value on Error

Specify whether to set the display for a computation error to [+Over] or [–Over].

• Overflow Sum, Ave

Specify how to handle

overflow data when it is detected in the SUM or AVE

computation of TLOG or CLOG. This setting is also applied to report generation.

Settings

Description

Error

Sets the computed result to computation error.

Skip

Discards the overflow data and continues the computation.

Limit

Uses a limit value in place of the overflow data and continues the computation.

• Overflow Min, Max, P-P

Specify how to handle overflow data when it is detected in the MAX, MIN, or P-P

computation of TLOG or CLOG. This setting is also applied to report generation.

Settings

Description

Over

Uses the overflow data as-is.

Skip

Discards the overflow data and continues the computation.

• Report (1 to 4)

Select the type of data to output as reports.

Settings

Description

OFF

Does not output reports. You cannot set Report 1 to [OFF].

Ave

Outputs the average value.

Max

Outputs the maximum value.

Min

Outputs the minimum value.

Sum

Outputs the sum value.

Instant

Outputs the instantaneous value.

• File kind

Specify the method used to create report files.

Settings

Description

Split

Saves each type of report to a separate file.

Combined

Saves the report data of two types in a single file.

Separate2

Saves a collection of reports, such as the hourly reports for a day or the daily
reports for a month, to a file (release numbers 4 and later).

• Template Function (Release numbers 4 and later)

You can create report templates in XML spreadsheet format and use them to
automatically create custom report files. To use templates, select [ON]. This setting is
fixed at [OFF] when [File kind] is set to [Separate2].

7.7 Setting DX1000/DX2000

Advertising
This manual is related to the following products: