Reference Deviation

Turn the reference deviation on or off, and specify the value with the measurement

input span one-digit EUS (100.0%). With style number S1 (system setting), it is not

displayed if the PID number is 1. With style # S2, it is not displayed when the PID

number is 2 or less.

Linearize

Mode

Select the linearize mode from [OFF], [Biasing], or [Approximation].

Input

Enter the linearize input value. (The value depends on the linearize mode.)

Biasing:

Set with the measurement input span EU (–5.0 to 105.0%).

Approximation: Set with the measurement input span EU (–5.0 to 105.0%).

You must set between 2 and 11 points total.

Output

Enter the linearize output value. (The value depends on the linearize mode.)

Biasing:

Set with measurement input span EUS (–100.0 to 100.0%).

Approximation: Set with measurement input span EU (–5.0 to 105.0%).

Note

• For linear biasing, set the values so that input + output is EU (0 to 100%). In addition, set

the values so that input + output is greater than or equal to the previous input + output.

• Set the approximation output to be greater than or equal to the previous value.

• If a value smaller than the previous value is specified for the third point or later, the settings

after that point are invalid.

• When the PV/SP math function is ON, the settings above are entered using [Control input

channel] items under the [Setting] tab for each control input channel. For the setting

procedure, see page 7-195.