Setting the Recorder

7.8 Setting MV1000/MV2000

Report

Specify the settings for sending e-mail when reports are created.

• Recipient1 and Recipient2

Set the recipients. For Recipient1 and Recipient2, select On to send e-mail or OFF to

not send e-mail.

• Include source URL, Subject, and Header

These items are the same as the e-mail that is sent when an alarm occurs. The
default subject is Report_data.

SNTP Client

• Use

Select [Use] to use the SNTP client function; Otherwise, select [Not]. If you select [Use],

the SNTP client settings are displayed.

• Server Name

Set the SNTP server name using up to 64 alphanumeric characters.

• If the DNS is used, you can set the host name as a server name.

• You can also set the IP address. In this case, the DNS is not required.

• Port No.

Enter the port number of the file transfer destination SNTP server in the range of 1 to

65535. The default value is 123.

• Access Interval

Set the time interval for synchronizing the time with the server to OFF, 1, 8, 12, or 24h.

If you select OFF, you can synchronize the time manually by operating soft keys. The

time is not synchronized if the difference in the time between the MV and the server is

greater than or equal to 10 minutes.

• Ref. Time

Set the reference time for making queries.

• Access timeout

Set the time to wait for the response from the SNTP server when querying the time to

10, 30, 90s.

• Time adjust (start)

Select [On] to synchronize the time using SNTP when memory start is executed;

Otherwise, select [OFF].