Index – Yokogawa DAQWORX User Manual

Page 227

Advertising
background image

7-51

IM WX101-01E

1

2

3

4

5

6

7

8

9

Index

Setting the Recorder

Partial (Partial Expanded Display)

Bound position (%)

Set the boundary for the partial expanded display. The range is from 1 to 99%.

Boundary

Set the value that is to be the boundary between the reduced section and the expanded

section in the range of “minimum span value + 1 digit to maximum span value – 1 digit.”

For channels that are set to scaling, the selectable range is “minimum scale value + 1

digit to maximum scale value – 1 digit.”

Example: Input range: –6 V to 6V. Bound position: 30. Boundary: 0

The –6 V to 0 V range is displayed in the 0% to 30% range, and the 0 V to 6

V range is displayed in the 30% to 100% range.

The conditions used to set the boundary vary depending on the measurement and

computation channels as follows:

• Measurement channel

When SCALE and SQRT are not used: Span L < boundary < span U

When SCALE and SQRT are used:

Scale L < boundary < scale U

• Computation channel

Span L < boundary < span U

Note

For the DX1000/DX2000, this is when [Partial] is turned [ON] under [Detail Setting] in the [Basic

Setting] tab.

Color (Display Color)

You can select the display color of each channel from 24 colors.

Green Band

Displays a specified section of the measurement range using a color band on the scale.

This setting is common with the bar graph display.

Region (Band area)

Settings

Description

Inside

Displays the area inside using the color band.

Outside

Displays the area outside using the color band.

OFF

Disables the function.

Color

Set the display color.

L and U

Specify the display position. Set a value within the span or scale range.

L: Lower limit of the area.

U: Upper limit of the area.

7.7 Setting DX1000/DX2000