Yokogawa DAQWORX User Manual

Page 262

Advertising
background image

7-86

IM WX101-01E

Alarm

Reflash

To set the reflash operation on the alarm output relay, select [ON]. The reflash function
is set on the first three output relays.

Settings

Description

Off

Reflash is not used.

On

*1

Reflash is used. The relays are deactivated for approximately 500 ms.

500ms

*2

Reflash is used. The relays are deactivated for approximately 500 ms.

1s

*2

Reflash is used. The relays are deactivated for approximately 1 s.

2s

*2

Reflash is used. The relays are deactivated for approximately 2 s.

*1 Release numbers 3 and earlier
*2 Release numbers 4 and later.

Rate of Change Decrease

Set the interval for the rate-of-change calculation of the low limit on rate-of-change alarm
in terms of the number of sampled data points (1 to 32). The actual interval is obtained
by multiplying the value specified here by the scan interval.

Rate of Change Increase

Set the interval for the rate-of-change calculation of the high limit on rate-of-change
alarm in the same manner as the interval for the low limit on rate-of-change alarm.

Hold

You can choose to make the alarm displays behave in the following ways. When you
use the alarm annunciator function (release number 3 or later), the setting follows the
annunciator sequence.

Settings

Description

Unhold

Clears the alarm indication when the alarm condition is released (returns to
normal condition).

Hold

Holds the alarm indication until an alarm acknowledge operation is performed.

Internal Switch AND

Select the internal switches that are to operate using AND logic. Set the range of internal
switches (from the first internal switch) to take the AND logic. All subsequent switches
will be set to OR logic.

7.7 Setting DX1000/DX2000