Index – Yokogawa DAQWORX User Manual

Page 263

Advertising
background image

7-87

IM WX101-01E

1

2

3

4

5

6

7

8

9

Index

Setting the Recorder

Relay AND

Select the relays that are to operate using AND logic. Set the range of relays (from the
first alarm relay) to take the AND logic. All subsequent relays will be set to OR logic.
Available settings are [None], [I01] (I01 only), [I01-I02] (I01 and I02), [I01-I03] (I01 to I03),
etc. Only alarm output relays that are installed are valid.

Relay action

Select whether the alarm output relay is energized or de-energized when an alarm
occurs. The setting applies to all alarm output relays.

Relay hold

You can choose to make the alarm output relays behave in the following ways. This
setting applies to all relays. When you use the alarm annunciator function (release
number 3 or later), the setting follows the annunciator sequence.

Settings

Description

Unhold

Turns the output relay OFF when the alarm condition is released (returns to
normal condition).

Hold

Holds the output relay at ON until an alarm acknowledge operation is performed.

Relay Action on ACK
You can use this setting on DX firmware version 2.0x or later. When you use the alarm
annunciator function (release number 3 or later), the setting follows the annunciator
sequence.

Settings

Description

Normal

The relay output is deactivated when the alarm ACK operation is executed. If the
condition for activating the alarm output relay is met in the next scan interval, the
relay output is activated.

This operation is valid only when the alarm output relay is set to [Hold].

Reset

The relay output is deactivated when the alarm ACK operation is executed. If a
new condition for activating the alarm output relay, the relay is activated.

Note

When reflash is turned ON, the operation of the first three output relays is set to nonhold.

Specifying Hold produces no effect.

Measure channel High/Low

Sets the hysteresis width of the alarm occurrence/release of the high/low limit alarm

specified on measurement channels.

Selectable range: 0.0% to 5.0% of the span or scaling width

Measure channel Delta High/Low

Sets the hysteresis width of the alarm occurrence/release of the difference high/low limit

alarm specified on measurement channels.

Selectable range: 0.0% to 5.0% of the span

Math channel High/Low, Ext channel High/Low

Sets the hysteresis width of the alarm occurrence/release of the high/low limit alarm

specified on computation and external input channels.

Selectable range: 0.0% to 5.0% of the measurement span

7.7 Setting DX1000/DX2000

Advertising
This manual is related to the following products: