7-155

IM WX101-01E

1

2

3

4

5

6

7

8

9

Index

Setting the Recorder

7.8 Setting MV1000/MV2000

MODBUS Client

Changes the upper/lower display area

Click to display the channel selection screen

Communication interval

Set the read cycle to 125ms, 250ms, 500ms, 1s, 2s, 5s, or 10s.

Auto recovery

Set the interval for retrying the connection when the connection is interrupted for some

reason. Select OFF, 10s, 20s, 30s, 1min, 2min, 5min, 10min, 20min, 30min, or 1h.

Modbus Server setting
• Server No.

Select from 1 to 16 for the server registration numbers to be configured.

• Port No.

Enter the port number in the range of 0 to 65535 for the selected server. The default

value is 502.

• Host Name

Set the destination Modbus server name using up to 64 alphanumeric characters.

• If the DNS is used, you can set the host name as a server name.

• You can also set the IP address. In this case, the DNS is not required.

• Unit

Select [Auto] if the unit number of the destination server is not required; Otherwise,

select [Fixed]. If you select [Fixed], the [Unit No.] item is displayed.

• Unit No.

Enter a fixed unit number in the range of 0 to 255.

Command setting
• Client command No.

Select from 1 to 16 for the transmitted command numbers to be configured.

• Command

Set the command type.

Settings

Description

Read

Read to the external input channel (16-bit signed integer type) from the server.

R-Math

Read to the communication input data (32-bit floating point type) from the server.

Write

Write the measurement channel (16-bit signed integer type) to the server.

W-Math

Write the measurement channel (32-bit signed integer type) to the server.

[Read] can be selected on MV2000s with the external input channel (/MC1 option) installed.

[R-Math] and [W-Mat] can be selected on models with the computation function (/M1 or

/PM1 option) installed.