Index – Yokogawa DAQWORX User Manual

Page 243

Advertising
background image

7-67

IM WX101-01E

1

2

3

4

5

6

7

8

9

Index

Setting the Recorder

Annunciator (Release number 3 or later)

These settings are activated when the annunciator mode is set to [ON] (by accessing

[Basic Setting] > [Alarm] > [Alarm action] > Annunciator mode]).

Click here to open the channel

selection dialog box

Click the desired channel

numbers to select them

Click here to open a dialog box

for specifying a comment text

block

Enter values in the [Comment

txt block no] boxes, check the

character strings that appear,

and click OK

Number

The position of the annunciator window.

Model

Displayed Windows

DX1000

24 or less

DX2000

80 or less

Use

Set the annunciator position that you want to use to [ON].

Starting with 1, consecutively set all annunciator positions that you want to use to [ON].

After a position has been set to [OFF], all of the positions after it will also be turned off

even if they are set to [ON].

CH No. and Level

You can assign alarms to annunciator windows by specifying channel numbers and alarm

levels.

You can set [Level] to [1], [2], [3], [4], or [All]. If you select [All], all of the alarms in the

specified channel are assigned to the specified window.

Comment txt block No.

You can select a text string (label) to display in the annunciator window by selecting a

comment text block number.

7.7 Setting DX1000/DX2000

Advertising
This manual is related to the following products: