2.2

Preparing the Recorder

Before starting DAQLOGGER, set recorder’s communication parameters then connect

the recorder to the PC.

For µR1000/µR1800/VR100/VR200

Settings for RS-422 communication

Provide the following settings.

• Baud rate:

9600 bps

• Data length:

8 bits

• Parity:

None

• Stop bit:

1 bit

• Address:

Set a unique address to each recorder.

See the Communication Function Manual of the recorder (IM 4D5B1-10E, IM 4H3B1-

10E, or IM 4N1A1-11E).

For DX100/DX200/DX200C/MV100/MV200/MV1000/MV2000/CX1000/CX2000/
DX1000/DX2000/DARWIN

Settings for Ethernet communication

For a model capable of Ethernet communication, set the following items.

• IP address

• Subnet mask

• Default gateway

Settings for RS-232 communication

For a model capable of RS-232 communication, provide the following settings.

• Baud rate:

38400 bps

• Data length:

8 bits

• Parity:

None

• Handshake:

CR:RS

• Protocol:

Normal (for DX/MV/CX)

• Stop bit:

1 bit (fixed to 1 bit on DX/MV/CX)

Settings for RS-422/RS-485 communication

For a model capable of RS-422A/485 communication, provide the following settings.

• Baud rate:

38400 bps

(9600 bps when connecting µR and VR recorders on a single multidrop line.)

• Data length:

8 bits

• Parity:

None

• Address:

Set a unique address to each recorder.

• Protocol:

Normal (for DX/MV/CX)

• Stop bit:

1 bit (fixed to 1 bit on DX/MV/CX)

For more details about communication settings, see the Communication Function Manual

for the recorder (IM 04L02A01-17E, IM MV100-17E, IM DA100-11E, IM DR231-11E, IM

DC100-11E, IM 04L31A01-17E, IM 04L41B01-17E, or IM MV1000-17E).