Index

Setting the Recorder

• WR_TRIG : Saves measured/computed data on the built-in RAM disk.
• RD_TRIG : Reads measured/computed data from the built-in RAM disk.
• LD_TRG1-3 : Reads setup data from the built-in RAM disk.
DC100
• DATA_WR : Writes the data for one scan (one data/channel) retained at the

generation of an event. To execute this, it is necessary to set LOGIC to the writing

period.

• TRIG : Generates a trigger to start writing. To execute this, it is necessary to set

TRIG to WRITE TRIG.

• START : Opens a file and starts the writing operation. It is the same function as the

START key on the operation panel.

• PAUSE : In the case of edge action, writing is suspended at the generation of

an event. In the case of level action, by setting the alarm, remote, relay or internal

switch to the event, writing is suspended at the detection of an event and resumes at
the resetting of the event (see the following figure). Setting the timer, match time or
manual function key to the event repeats suspension and resumption of data writing at

the generation of each event.

• CP_FDD : All files in the built-in RAM disk are copied on a floppy disk. Whether to

cancel files after copying or not depends on the setting in the MEM SET of the SET
UP menu. Copying after a conversion to ASCII format cannot be done.

• CP_SCS0 to CP_SCS7 :
All files in the built-in RAM disk are copied on a MO, ZIP or PD. Whether to cancel

files after copying or not depends on the setting in the MEM SET of the SET UP menu.
Copying after a conversion to ASCII format cannot be done.

Displayed only on models with the C/5 option. SCS0 to SCS7 represent the SCSI ID

numbers. Check the ID numbers of SCSI devices that are connected, because ID

numbers are displayed even if there are no devices connected to them.

FLAG (only for Math option models; DC style no. 7+, DA100/DR style no 8 or higher)
• F01 to 16 : Set the flag number (F01 to F16) to 1. F01 to F16 are normally 0. Flags

can be placed in computing equations to hold the computed result using a certain

event as a trigger, or reset to 0.

FLOPY
• LD_TRG1-3 : Reads setup data from the floppy disk.
SCSI0 to SCSI7 (for DC100 with /C5 option only)
• LD_TRG1 to 3 : Read setup data from the SCSI device (MO, ZIP or PD).

SCSI0 to SCSI7 represent the SCSI ID numbers. Check the ID numbers of SCSI

devices that are connected, because ID numbers are displayed even if there are no

devices connected to them.

REPORT (available if the instrument is equipped with the REPORT function.)

• START (Edge action) : Starts making up a report.

• STOP (Edge action) : Stops making up a report.

(No Start/Stop for Level action)

Basic Setup for hourly, daily, or monthly report function must be ON.

• REPORT (Level action) :

Starts/stops making up a report.

Note

If, in the SETUP mode, the report function is set to OFF for all data items, you cannot select the

action item REPORT.

7.9 Setting DARWIN