Setting relay and internal switch actions – Yokogawa DAQWORX User Manual

Page 362

Advertising
background image

7-186

IM WX101-01E

Setting Alarm Interval, Hysteresis, and Alarm Display Hold

Select a SETUP topic

SETUP tab

Alarm display hold

(only DC100/DR)

RH alarm interval

RL alarm interval
Hysteresis setting

Alarm Interval

For high/low limit on rate-of-change alarms, variation is measured over a preset interval.

Hysteresis

Set the width between the value of alarm occurrence and its release. Hysteresis values

can be set in the 0-1% percentage range of the span. The hysteresis setting is used for

high and low limit alarms.

Alarm Display Hold (DC100, and DR only)

For DC100, and DR select whether to hold the alarm indicator after the alarm is released,

or not.

Setting Relay and Internal Switch Actions

Select a SETUP topic

SETUP tab

Relay AND/OR

Reflashing Alarm

Relay hold

Relay (De-)

Energizing

Reflashing Alarm Setting

When several alarms share the same alarm output relay, you can select this setting

which results in a short de-operation of the relay when a second alarm occurs.

Relay AND/OR

Select how the internal switches/alarm output relays will be operated, when a group of

alarms share the same internal switch or alarm output relay.

AND: will be operated when all alarms are occurring;

OR: will be operated when at least one alarm is occurring.

7.9 Setting DARWIN